Safety and Fire Protection System

 
 
Safety and Fire Protection

Explosion Proof Truck
The first explosion proof VNA (Very Narrow Aisle) turret forklift truck in Thailand. CTX 1300 SE : Articulated chassis gives excellent maneuverability and manup turret truck picking type Pyroban : System 4000 gas detection system and explosion proof motors.

First Automatic Fireproof Door System

First system operates when the Fuse connected to the door on one end and the counter weight on the other, breaks at 55°C and the door close.

Second Automatic Fireproof Door System

Second system operates when the smoke detector situated outside the room or heat detector situated in the room, detects smoke or heat, it will send a signal to the controller and release the door.
 
 
Sprinklers with Fragile Bulb
The sprinklers with fragile bulb are installed in harzardous chemicals storage areas such as flammable liquid, poisonous chemicals and oxidizing agent in Zone A, B, E, F, G, I and K. This fragile bulb will be cracked when the room temperature reaches 68°C and then water and foam will be sprinkled out at ratio of 97 to 3.

Emergency Exit Door

These doors are installed at the hazardous chemicals areas such as Zone A, B, J, K and L. It is also installed at our mini lab and training. The emergency exit doors are fire proof.
 
Sprinklers with Fragile Bulb
Sprinklers with Fragile Bulb  
Other Safety Equipment
  • Foam Tank (used for containing foam to extinguish fire)
  • Controlling valves for switching on and off (water pump)
  • .Pre-action control panel (control the deluge valve opening)
  • Extinguishers, which are installed all around the Chemicals Distribution Center.
  • Electronic lightning equipment
  • Emergency light at the hazardous zones
  • Personal protection equipment (P.P.E.)

Emergency Shower

This shower is used to wash people with a large amount of water when chemicals are accidentally poured on someone.
 
Emergency Shower
Emergency Shower  
Under ground pump room & water tank
This water tank contains water of up to 400,000 liters and a Bag tank which contains 3,570 liters of compressed protein foam for extinguishing fire.There are 3 types of pump:
 
 
Safety and Fire Protection

Working System of Fire-protection System at the Chemicals Distribution Center
When the temperature reaches 55°C, the door will shut automatically. And when the temperature increases up to 68°C, the fragile bulb in the sprinklers will melt. Then the pressure in the fire fighting line will be dropped to 100 PSI and the jogging pump will immediately start to pump to maintain the pressure. If the pressure is continuously decreased to 85 PSI, the jogging pump will stop working and the diesel pump will start working instead. It will pump water and foam in the ratio of 97 to 3 to the sprinklers. Electric system in Zone A, B, E, F, G, I and K is explosion proof and in Zone C and D is normal waterproof type.
 
Safety and Fire Protection